Skip to main content

Menghitung Short Circuit calculation Menggunakan MVA method (manual)

Maaf saya tulis dalam bahasa inggris, karena ini saya belajar dari literatur berbahasa inggris.



Utility: 150KV, 1000 MVAsc
Transformer 1: 170 MVA, 150/13.8KV, 15% Z


13.8KV Bus
Generator: 100MVA, X"d = 0.2
Transformer 2: 30 MVA, 13.8/6.6KV, 15% Z


6.6KV Bus
Transformer 3: 2MVA, 6.6KV/400V, 10% Z
Motor 1: 10 MVA (Lumped), 20% Z


400V Bus
Motor 2: 1000 KVA (Lumped), 20% Z
Motor 3: 600 KVA (Lumped), 10% Z






In the event of a short circuit, the sources of short circuit current are
1. Utility
2. Generators
3. Motors


Static loads such as heaters and lighting do not contribute to short circuit.
"EquivalentMVA" are:
Transformers and Motors

Generators


Cables and Reactors



So, here are the results of MVAsc:
Utility: MVAsc = 1000MVA
Transformer 1: MVAsc = 170 / 0.15 = 1133.33 MVA


13.8KV Bus
Generator: MVAsc = 100 / 0.2 = 500 MVA
Transnformer 2: MVAsc = 30 / 0.15 = 200 MVA


6.6KV Bus
Transformer 3: MVAsc = 2 / 0.1 = 20 MVA
Motor 1: MVAsc = 10 / 0.2 = 50 MVA


400V Bus
Motor 2: MVAsc = 1 / 0.2 = 5 MVA
Motor 3: MVAsc = 0.6 / 0.1 = 6 MVA

Now we calculate the upstream contribution :
At Transformer 1:
MVAsc @ 150KV = 1000 MVA
MVAsc @ 13.8KV = 1/ (1 / 1000 + 1 /1133.33) = 531.25 MVA


At Transformer 2:
MVAsc @ 13.8KV = 531.25 + 500 = 1031.25 MVA
MVAsc @ 6.6KV = 1/ (1 / 1031.25 + 1 / 200) = 167.51 MVA


At Transformer 3:
MVAsc @ 6.6KV = 167.51 + 50 = 217.51 MVA
MVAsc @ 400V = 1/ (1 / 217.51 + 1 / 20) = 18.31 MVA


At 400V Motors
Motor 3: MVAsc = 18.31 x 5 / ( 5 + 6 ) = 8.3 MVA
Motor 4: MVAsc = 18.31 x 6 / ( 5 + 6 ) = 9.98 MVA
The fault MVAsc @bus 400V = 18.31 + 5 + 6 = 29.31MVAsc
The three phase If = 29.31/(1.732*(0.4)) = 42.3 kA.




Now we come to fault single phase to ground :
For single phase faults, positive sequence, negative sequence and zero sequence
impedances need to be calculated.
If = 3 (I1 + I2 + I0)


Examining the circuit in above, at the 400V Bus, on Transformer 3 contributes to the
zero sequence current.


For transformers, the negative sequence and zero sequence impedance are equal to the positive sequence impedance.


Z1 = Z2 = Z0 or
MVA1 = MVA2 = MVA0
@bus 400V;
1 / MVAsc =1/3 (1 / MVAsc1 + 1 / MVAsc2 + 1 / MVAsc0)
1 / MVAsc = 1/3 (1 / 29.31 + 1 / 29.31 + 1 / 20 )
1/ MVAsc =


MVAsc = 1/ = 25.4 MVAsc



If= 25.4 / (1.732 x 0.4) = 36.6 kA
http://news.chivindo.com/734/menghitung-short-circuit-calculation-menggunakan-mva-method-manual-.html

Comments

Popular posts from this blog

BT-BASIC commands used

8.10     Some of the most frequently used BT-BASIC commands used are: msi                               Changes default working directory. Mass storage is            Same as “msi” cat                               Catalogs (list)the node names in the specified directory.             get                               Brings the contents of a file into the system workspace.        ...

Perhitungan & Cara Merubah Kumparan Blender Dari 220 V Menjadi 12 V

          Seperti yang telah dijelaskan pada buku “menggulung motor listrik arus bolak-balik, servis peralatan listrik rumah tangga kelompok penggerak dan perbaikan peralatan listrik pertukangan”, bahwa motor penggerak yang digunakan pada perlatan listrik rumah tangga dan pertukangan seperti blender, mixer, bor tembak, gerinda dsb menggunakan jenis motor universal. Motor universal adalah jenis motor listrik yang dapat disuplai dengan sumber listrik arus bolak-balik (AC) dan arus searah (DC). Jadi peralatan-peralatan listrik rumah tangga dan pertukangan tersebut yang biasanya kita suplai dengan sumber listrik AC dari PLN atau Genset sebesar 220 V sebenarnya dapat juga kita suplai dengan sumber listrik DC yang tentunya tegangan juga harus sama yakni 220 V.           Yang menjadi permasalahan bagaimana kalau peralatan listrik rumah tangga atau pertukangan tersebut, sebagai contoh misalkan blender yang ingin digunakan atau dioper...

BT-BASIC command line

8.8       At the BT-BASIC command line type the command  msi  and the directory path, then press the “ENTER” key on the keyboard.  Example:                   msi ‘/hp3070/boards/aspect/main’ 8.9       At the BT-BASIC command line type the command  get ‘testplan’ and press the   ENTER” key on the keyboard.  You should now see the body of the testplan file displayed in the work space of the BT-BASIC window. 8.10     Some of the most frequently used BT-BASIC commands used are:

Autodesk SketchBook Pro 2021 Full Version

BAGAS31 – Sesuai dengan namanya, Autodesk SketchBook Pro 2021 Full Version ini merupakan software digital sketching atau drawing terbaik yang bisa kamu gunakan. Pada versi terbaru kali ini, ada beberapa penambahan fitur yang sangat efektif. Dengan fitur baru tersebut, diharapkan mampu meningkatkan proses sketching maupun drawing kamu. Autodesk SketchBook sendiri sudah bisa kamu dapatkan secara gratis melalui website resminya. Namun untuk kamu yang mau download versi Autodesk Sketchbook Pro, maka bisa langsung download melalui link yang sudah saya sediakan di bawah ini. Download Autodesk SketchBook Pro 2021 Full Version Screenshot: System Requirements: Windows 10 2.5 – 2.9 GHz of Intel or AMD CPU 4 GB of Memory 256 MB Graphics card with OpenGL 2.0 support We recommend that you use a pressure-sensitive tablet and pen for basic features Download: Autodesk SketchBook Pro 2021 Full Version [ FileUp ][ Uptobox ][ UsersDrive ] Jamu Only [ File...

Testhead

4.3         Testhead The testhead is that portion of the tester that supports the PIN, ASRU and Controller cards.   The testhead is divided into two BANKS and each BANK is divided into two MODULES, see figure 2 below.  Bank 1 contains modules 0 and 1, bank 2 contains modules 2 and 3.  The test fixtures are placed on the banks of the tester and locked down for board testing.  The testhead cards interface to the test fixture through the spring loaded pogo pin “nails” at the top edge on each of these card types. 4.4       Support Bay The support bay is a stand-alone cabinet that houses the power supplies for the Unit Under Test.  This bay also houses the test station power distribution unit and test station controller on earlier models. 4.5       Emergency Shutdown Switch The emergency shutdown switch is the large red button located at the lower left corne...

Kelebihan dan Kekurangan Saluran Listrik Jenis Saluran Udara dan Saluran Bawah Tanah

Berdasarkan pemasangannya,   saluran distribusi dibagi menjadi dua kategori, yaitu : saluran udara (overhead line) merupakan sistem penyaluran tenaga listrik melalui kawat penghantar yang ditompang pada tiang listrik. Sedangkan saluran bawah tanah (underground cable) merupakan sistem penyaluran tenaga listrik melalui kabel-kabel yang ditanamkan di dalam tanah. 1.    Saluran Bawah Tanah (Underground Lines) Saluran distribusi yang menyalurkan energi listrik melalui kabel yang ditanam didalam tanah. Kategori saluran distribusi seperti ini adalah yang favorite untuk pemasangan di dalam kota, karena berada didalam tanah, maka tidak mengganggu keindahan kota dan juga tidak mudah terjadi gangguan akibat kondisi cuaca atau kondisi alam. Namun juga memilik kekurangan, yaitu mahalnya biaya investasi dan sulitnya menentukan titik gangguan dan perbaikannya. Kedua cara penyaluran memiliki keuntungan dan kerugian masing-masing. Keuntungan yang dapat diperoleh dari suatu jaringan bawah...